Topology On-line double conversion Nominal power (kW)10-150 kW (parallel up to 450 [3 UPSs in parallel] kW)Modular elementsPower modules, static bypass switch module, intelligence moduleDisplay Color touch screen, 4.3 inches, status LED, mimic on displayCommunicationNetwork management card included with ethernet (SNMP) and Modbus 8 dry contacts (4 inputs, 4 outputs)Maintenance bypassInternal maintenance breaker Optional maintenance bypass panelParallel capabilitySimplified parallel (1+1 for redundancy); Up to 3 UPSs for capacity or 3+1 UPSs for redundancyDouble conversion modeYes, up to 97%ECO modeYes, up to 99%ECOnversion mode Yes, up to 99%Nominal input voltage 380/400/415 VInput voltage range (phase to phase)+/-15%Single mains/dual mainsSingle mains as standard. Easily converted to dual mains.Input frequency 40-70 HzInput power factor >0.99 @ load >25 %, >0.95 @ load > 15%Maximum short-circuit rating 65 kABackfeed protection Included Nominal output voltages 380/400/415 VLoad power factor PF=1 (0.7 leading to 0.7 lagging without derating)Voltage regulation +/- 1%Frequency 50 / 60 Hz +-0.1% free running Overload 1 min @ 150%; 10min @ 125%Output THDU on linear load <1%Nominal DC Bus480 – 576 V (at ratings 50 kW, 100 kW, 150 kW); 60 kW: 432 – 576; 384 – 576 V (at other ratings, including 60kW and 120kW)Charging power Charging power in % of output power at 0 – 40% load: 80% Charging power in % of output power at 100% load: 20% At 380 V only 15% for 50 kW, 100 kW, 150 kW.Acoustic noise 57 dB (70% load) / 65 dB (100% load)Dust protection Air filter included. Conformal coatingSeismicWith optional kit. OSHPD tested